Modular liquid level control relay, Harmony, 5A, 2CO, 24...240V AC DC
Excl. Tax
Excl. Tax
All Sellers
Seller | Price | Delivery | Shipping Cost | ||
---|---|---|---|---|---|
View Seller Profile
B2B Network
|
|
Shipping Cost
|
No sellers found for this product.
Modular liquid level control relay, Harmony, 5A, 2CO, 24...240V AC DC
Excl. Tax
Excl. Tax
Description
Product Details
Activity | IDSIG |
---|---|
Price | AEDÂ 292.72 |
Pincode Group | default |
Part Number | RM35LM33MW |
Rated current | 5:00 AM |
[Uc] control circuit voltage | 24...240 V |
[Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
[Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60255-5, 4 kV conforming to IEC 60664-1, 4 kV conforming to IEC 61000-4-5 |
[Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz +/- 10 % |
ambient air temperature for storage | -40-70 °C |
compatibility code | RM3 |
connections - terminals | screw connectors |
control circuit voltage limits | - 15 % + 10 % Un |
IP degree of protection | IP20 (terminals) conforming to IEC 60529, IP30 (casing) conforming to IEC 60529 |
marking | CE : 73/23/EEC, CE : EMC 89/336/EEC |
maximum switching voltage | 250 V AC/DC |
mechanical durability | 30000000 cycles |
minimum switching current | 10 mA at 5 V DC |
mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
operating position | any position without derating |
operating rate | <= 360 operations/hour full load |
overvoltage category | III conforming to IEC 60664-1 |
pollution degree | 3 conforming to IEC 60664-1 |
product certifications | CSA, GL, UL, C-Tick, GOST |
product or component type | level control relay |
range of product | Harmony Control Relays |
relative humidity | 95-95 % at 55-55 °C conforming to IEC 60068-2-30 |
supply voltage limits | 20.4-264 V AC/DC |
tightening torque | 0.6-1 N.m conforming to IEC 60947-1 |
utilisation category | AC-12 conforming to IEC 60947-5-1, AC-13 conforming to IEC 60947-5-1, AC-14 conforming to IEC 60947-5-1, AC-15 conforming to IEC 60947-5-1, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 60947-5-1 |
width | 35 mm |
contacts type and composition | 2 C/O |
Maximum power consumption in W | 1.5 W DC |
Reset time | 1750 ms |
Immunity to microbreaks | 100 ms DC, 90 ms AC |
Measurement error | 0.5 %/°C with temperature variation |
Switching capacity in VA | 1250 VA |
Nominal output current | 5:00 AM |
Housing material | self-extinguishing plastic |
Time delay type | adjustable 0.1...5 s, +/- 10 % |
Repeat accuracy | +/- 2 % for time delay |
Maximum switching current | 5 A AC/DC |
Functionality | resistive probe detection |
Output contacts | 2 C/O |
Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5, 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1 |
Relay monitored parameters | detection by resistive probes |
Maximum power consumption in VA | 5 VA AC |
Measurement range | 250 Ohm...1 MOhm |
Relay name | RM35L |
Relay type | level control relay |
Run-up delay at power-up | 0.6 s |
Cable capacitance | 1 nF at HS (High Sensitivity) for probe cable, 2.2 nF at St (Standard Sensitivity) for probe cable, 4.7 nF at LS (Low Sensitivity) |
Sensitivity scale | 0.25...5 kOhm LS (Low Sensitivity), 5...100 kOhm St (Standard Sensitivity), 50...1000 kOhm HS (High Sensitivity) |
Sensitivity adjustment | 5-100 % |
Maximum supply current for sensors | 1 mA |
electromagnetic compatibility | emission standard for industrial environments conforming to EN/IEC 61000-6-4, emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3, immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
ambient air temperature for operation | -20-50 °C |
standards | EN/IEC 60255-6 |
local signalling | LED (yellow) for relay ON, LED (green) for power ON, LED (yellow) for timer ON |
safety reliability data | B10d = 170000, MTTFd = 182.6 years |
insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5, > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1, > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5, > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1, > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5, > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
Measurement Accuracy | +/- 10 % of the full scale value, +/- 20 % for the HS range |
Electrical Durability | 100000 cycles |