Circuit breaker Easypact EZC100H - TMD - 40 A - 1 pole 1d

EZC100H1040
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Description

How to Video

Product Details

Price AED 210.18
Activity PPCCB
Pincode Group default
Part Number EZC100H1040
[ics] Rated Service Breaking Capacity 5 kA at 125 V DC conforming to IEC 60947-2, 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[ui] Rated Insulation Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
breaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2, 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity Code H
Circuit Breaker Name Easypact EZC100H
Connection Pitch 25 mm
Downside Connection front
Earth-leakage Protection without
Neutral Protection Setting without protection
Protected Poles Description 1t
suitability for isolation yes conforming to IEC 60947-2
Trip Unit Name TM-D
trip unit rating 40-40 A at 50 °C
trip unit technology thermal-magnetic
Upside Connection front
utilisation category category A
Weight 338.0 g
Package1 Length*Width*Height 13.8 cm x 9.5 cm x 3.2 cm
Country of Manufacturing Thailand
ambient air temperature for operation -25-70 °C
ambient air temperature for storage -35-85 °C
compatibility code EZC100
control type toggle
depth 60 mm
device application distribution
device short name Easypact EZC100H
Electrical Durability category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
height 130 mm
IK degree of protection IK07 conforming to IEC 62262
IP degree of protection IP20 conforming to IEC 60529
local signalling positive contact indication
Market Segment small commercial
mechanical durability 8500 cycles
mounting mode fixed
mounting support backplate
network frequency 50/60 Hz
network type DC, AC
Poles Description 1P
pollution degree 3 conforming to IEC 60664-1, 3 conforming to IEC 947-1
Product Name EasyPact EZC
product or component type circuit breaker
Protection Type short-circuit protection, overload protection
range EasyPact
range of product EasyPact
standards JIS C8201-2-2, EN/IEC 60947-1, GB/T 14048.2, EN/IEC 60947-2
width 25 mm
ambient air temperature for operation -25-70 °C
standards JIS C8201-2-2, EN/IEC 60947-1, GB/T 14048.2, EN/IEC 60947-2
local signalling positive contact indication
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2